The temperature transmitter converts the field resistance temperature detector (RTD) or thermocouple (TC) signal into a standard current signal of 4 to 20 mA for control and remote transmission. It supplies secondary instruments such as indication alarms, recorders, regulators, and DCS for measurement, indication, and process regulation.
Features
· Isolation type temperature transmitter: input/output signal isola tion, meeting 500V electrical isolation (input/output).
· High-performance precision conversion: stable and reliable, long service life.
· Internal/external cold junction compensation can be selected, with linear calibration and testing of various signal types.
· Fast response: the response time is within 500ms.
· It has strong anti-electromagnetic and radio frequency interference capabilities, and complies with IEC/EN61326 standards.
· Diagnosic function: self-fault diagnosis, sensor disconnection short circuit diagnosis, variable upper and lower limit detection and other diagnosis.
· Supports HART5/7 (optional). Through the HART interface, the temperature transmitter module can be configured and maintained for specific applications.
· Modular glue-filled packaging treatment, moisture-proof, anti-vibration, large temperature range, suitable for a vari ety of complex working conditions.
· Intrinsic safety explosion-proof and dust explosion-proof: suitable for explosive site installation and use.
Main Parameters
· Output signal: 4 to 20mA + HART
· Nominal voltage: 24 VDC
· Power supply: 17 to 40 VDC
· Alarm output: ≤ 3.8 mA or ≥ 20.5 mA
· Cold junction compensation: Support built-in / built-out, accuracy: ≤ 0.5°C
· Maximum consumption current: ≤3.15 mA
· Maximum load resistance: R = (U Power Supply-12) / 0.024
· Protection rating: IP20
· Galvanic isolation: 500 VAC (Input/Output)
· Insolation resistance: ≥ 50 Ω
· Response time: ≤ 500 ms
· Start delay: ≤ 6 s
· Connection type: 2-wire, 3-wire, 4-wire
Usage Environment
· Working temperature: -40°C to +85°C
· Storage temperature: -40°C to +85°C
· Relative humidity: 5% to 95%
· Atmospheric pressure: 86 kPa to 106 kPa
Safety Approval
· Explosion-proof grade: Ex ia IIC T4/T6 Ga, Ex ia llC T85°C/T135°C Db
· Explosion-proof certificate: GYB23.2660X
· Certification standard: GB3836.1, GB3836.
Application
· Temperature transmitter, divided into HART® communication and USB version, converts different types of input signals into 4 to 20 mA analog output signals.
· AW201 temperature transmitter with HART® communication features, excellent performance, long-term high stability, and high measurement accuracy, equipped with advanced diagnostic functions.
· Universal input signal: connect resistance temperature detector (RTD), thermocouple (TC).
Model Code
Model Type |
Code |
Description |
Type |
AW 201 - A01 |
4 to 20 mA + HART |
Configuration software |
+1 |
Unavailable |
+2 |
AW Tool |
Calibration certificate |
A |
Unavailable |
B |
5-point calibration certificate |
Transient protect |
T |
Integral transient protector |
Input (configuration) |
1 |
Configue according to customer requirements |
2 |
Pt100, 3-wire, 0 to 100ºC |
Output |
S |
4 to 20 mA, 2-wire |
Packaging & Delivery
Category |
Product Size |
International Commercial Terms (Incoterms) |
Terms of Payment |
Nearest Port |
AW201 |
6 cm * 6 cm * 5 cm |
CIF, CFR, DAP |
LC, T/T, D/P |
Shanghai, Guangzhou,Tianjin |
Related Products
AW202 Temperature Transmitter Module